Specifications include, but are not limited to: Vendor is responsible for full and complete fire panel replacement which shall include all devices; intelligent power expander, photo detector, detector base, point addressable fire panel, lcd remote annunciator red enclosure, heat detector, duct detector with relay, addressable pull station dual action, input module, relay module, wall selectable horn/strobe - red, power supplies, panel cabling, and any other device needed for a functioning system under NFPA standards. 1.2.2. Currently installed fire devices are ESTIMATED and all devices that are currently installed will need to be replaced so that existing fire protection coverage is the same after update. 1.2.3. Vendor will ensure new system will function and cover the exact same area which is currently monitored. 1.2.3. Necessary Hardware, Cabling, and Equipment to install Magnet Hold Opens on existing Fire Doors in 22 locations. 1.2.3.1. Necessary Hardware to include, wall mount magnets for magnetic door hold opens, door mount plate and bar for magnetic door hold opens, electrical relays to properly operate and control magnetic door hold opens, and power supplies to operate and control magnetic door hold opens. 1.2.3.2. Will need to connect to main fire panel or Extender panel in outer buildings on campus. Hardware is to be mounted to the door and the wall. Run Wiring to power supplies and magnetic door hold open control panels so that the magnets will release and the doors automatically close in a fire event on fire panel. 1.2.4. Hardware, cabling, and equipment to install 4 Heat Detectors and 3 pull stations in Mechanic Maintenance Garage and Office. 1.2.4.1. This is currently monitored on the panel and is attached to the same building the main panel is in. Will be a separate NAC-Node on the panel. Run necessary wiring to equipment so that the new devices will operate properly on fire panel system. 1.2.4.2. Necessary Wiring to meet or exceed NFPA and NEC standards and are currently specked at 14/2 red non-plenum shielded cabling for this location. 1.2.4.3. The Maintenance Garage is an open ceiling, block wall metal hoop structure and all devices will be surface mounted to the block wall or the metal trusses of building. 1.2.4.5. The office space has a drop ceiling and framed walls. Vendor shall mount devices to wall or to drop-down ceiling. All mounting hardware, conduit, electrical boxes, mud rings, and fasteners shall be provided and installed by vendor. Vendor will ensure devices are mounted securely in all locations.